Modular Scalable Platform

The modular platform comes equipped with a wide range of advanced control functionality including full circles 360 degrees real and reactive power control. It can do both grid following as well as grid forming, making it suitable for use in various applications. Moreover, it has applied parallel operation technique up to 16 units and it can allow customers to choose capacity from 200kVA up to 3.2MVA. The optimal parallel operation method not only increases the efficiency but also improves the reliability of an overall system.

Features

Powerful

  • Industry-leading power density
  • Parallel-able up to 16 inverters
  • Suitable for wide range of project sites

Flexible

  • Standard 19’’ rack
  • 480/600/690 VAC
  • Easily configurable into any size inverter by modular scalable platform

Reliable

  • Air-cooled with a wide temperature range
  • Optimize efficiency and increase longevity with master controller
  • Keep operating in case one inverter goes down

Increased longevity via intelligent cycling of inverters

  • Measure running fatigue from running time
  • Increase total system life with rotated running of string inverter
    within fans and capacitor’s limited life-time

Specification

CategorySpecifications
Product NameModular Scalable String Platform
Model NameLSPB-PA-0180-4-1
Electrical
Spec.
Number of Phases3 phase 3 wire system
Operation MethodGrid-connected / Stand-Alone
InputInput Voltage 1)730 ~ 1,500 VDC (@ 480 VAC) / 900~1,500 (@600VAC) /
1,035 ~ 1,500 VDC (@ 690 VAC)
Maximum Input Current205 A(@ 480 VAC) / 200 A (@600VAC) / 193 A (@ 690 VAC)
Short Circuit Current / Interrupting CapabilityApprox. 3 kA / 85 kA
Control MethodActive/reactive power control
OutputRated Capacity 1)150kVA (@ 480VAC) / 180kVA (@600VAC) / 200kVA (@690VAC)
Rated Voltage3ø 3w 480/600/690 VAC
Rated Frequency60 Hz
Rated AC Current180Arms (@480VAC) / 173Arms (@600VAC) / 167Arms (@690VAC)
Maximum AC Current205 Arms(@ 480VAC) / 197 Arms(@ 600VAC) / 190 Arms(@ 690VAC)
Short Circuit Current / Interrupting CapabilityApprox. 2 kA / 70 kA
Current DistortionTHD <5%, Individual harmonic distortion <3%
Power Factor1.0 leading to 1.0 lagging
EfficiencyMaximum > 98% / Round Trip > 96.5%
ControlStandby Power27 W (for PWR on standby)
Control Power24VDC / 140W(for PWR FAN), 75W(for PWR)
Max Back Feed Current0A
Output Fault Current(TBD)
Max Output Over Current Protection510 A (200% of Rated Current)
Trip Limit & Trip Time Accuracy1% of Rated current or voltage, 100ms
Dimensions & Environmental
Spec.
Dimensions (WxHxD)483 x 264 x 843 mm [19’’x10’’x33’’] / 19’’ 6U Standard Rack
Weight (kg)Approx. 120kg [265lbs]
Cooling MethodForced air cooling
Enclosure RatingNEMA Type 1 / Indoor type
Noise LevelMax 80dB
Operating Temperature-20°C to 55°C (Power Derating 2%/°C above 50°C. 90%(power at 55°C)
Relative HumidityRH < 95% (Non-Condensing)
Storage Temperature-20℃ ~ 70℃
Elevation < 1,000m
User InterfaceCommunicationModbus TCP(Remote Update) / Modbus RTU
StandardsSafetyUL1741 SA including CA Rule21, CSA-22.2
EMCEN55011, EN61000-6-2
HarmonicsIEEE1547

1) For 480/690Vac, UL certified TBD.



(Unit: kVA)

<!-- --> <!-- -->
Number of Parallel unit12345678
Number of Parallel unit12345678
480Vac15030045060075090010501200
600Vac180360540720900108012601440
690Vac2004006008001000120014001600
Number of Parallel unit910111213141516
Number of Parallel unit910111213141516
480Vac13501500165018001950210022502400
600Vac16201800198021602340252027002880
690Vac18002000220024002600280030003200

More Information

All in one

Hanoi Office

10th floor, 789 building, 147 Hoang Quoc Viet street, Cau Giay District, Ha Noi city, Vietnam

Bac Ninh Factory

KCN Yên Phong Mở Rộng, Lô CN11-3, 3-4, Yên Phong, Bắc Ninh, Việt Nam

Hai Phong

LGE Factory - Tràng Duệ Industrial - An Dương District, Hải Phòng City

Ho Chi Minh Office

17th floor, Empress building, 138-142 Hai Ba Trung street, Da Kao ward, Distric 1, Ho Chi Minh city, Vietnam

Log in

Welcome to LS Electric