GIPAM1000

Multifunctional digital power protection monitoring device with various protection elements and measurement elements

Features

Protection function

  • With 24 types of protection elements in 2 models, the distribution system protected
  • Enhanced analysis function through various saved event data (up to 1,000 events are saved)
  • Simple Trip logic Function
  • Select Before Operating (SBO) and Check Before Operating (CBO)
  • Vector diagram
  • Sequence of Event (SOE)
  • PT (VT) failure detection
  • Circuit Breaker Failure (CBF)
  • Disk emulation

Convenience function

  • Self-diagnosis and sequence monitoring
  • HMI with enhanced visibility and convenience
  • Long-life and reliable parts applied

Communication function

  • Universal communication (MODBUS/RS-485)

Specification

Protection

TypeUsageProtection Elements
GIPAM1000 FIFeeder (13 Type)OCR (50/51)
UVR (27)
LOCK-OUT (86)
OCGR (50N/51N)
OVR (59)
CBF (50BF)
SGR (67G)
OVGR (64)
PTF (60F)
SEF (51S)
POR (47P)
GIPAM1000 DGDistributed Generator
(25 Type)
OCR (50/51)
UVR (27)
LOCK-OUT (86)
DOCGR (67NI/ND)
UFR (81U)
UCR (37)
OCGR (50N/51N)
OVR (59)
CBF (50BF)
DPR (32P)
OFR (81O)
WS (78V)
SGR (67G)
OVGR (64)
PTF (60F)
DQR (32Q)
ROCOF (81R)
SEF (51S)
POR (47P)
SYNC (25)
DOCR (67I/67D)
UPR (37P)

Specification

TypeSpecification
Wiring3P3W (2PT-D), 3P4W (3PT-Y)
RatingFrequancy60Hz, 50Hz Note)
VoltagePT110V (55~125V)
GPTVn*√3 Vn: PT secondary rating voltage
CurrentCT5A
ZCT1.5mA
PowerAC/DC110V, DC125V
Power consumption30W or less: Stanby / 50W or less: Operation
Burden0.5VA or less: PT
1.0VA or less: CT
Input contactfor generalDigital Input AC/DC 110V, DC125V
Output contactfor tripAC 250V 15A/DC 30V 15A, Resistive Load: Rated Capacity
AC 4000VA, DC 480W: Opening Capacity
for alarmAC 250V 10A/DC 30V 10A, Resistive Load: Closed Capacity
AC 1250VA, DC 150W: Opening Capacity
ToleranceOperation Value±5%
Operation Time±5% or ±35ms
OInsulation ResistanceDC 500V 100MΩ or more
Insulation VoltageAC 2kV (1kV)/1min
Lightning impulse voltageAC 5kV (3kV) or more, 1.2x50μs standard waveform supplied
Overload withstandCurrent circuitWithstand 1.2 times of rated current continuously
Withstand 2 times of rated current for 3 hours.
Withstand 20 times of rated current for 2 seconds.
Withstand 40 times of rated current for 1 second.
Voltage circuitWithstand 1.15 times of rated voltage for 3 hours.
Fast Transient Disturbance4kV: power input
2kV: other input
Electrostatic Discharge (ESD)8kV: Air, 6kV: Contact
TemperatureOperation-25℃ ~ 60℃
Storage-40℃ ~ 70℃
HumidityRH 80% or less (non-condensing)
Altitude2,000m or less
EnvironmentA place not subject to abnormal vibration and shock.
Applied StandardsKEMC 1120
Dimension (mm)196 (W) x 254 (H) x 220 (D): Cutting Size
Weignt6.78kg
CommunicationRS-485: Modbus

Note) Contact us.

All in one

Hanoi Office

10th floor, 789 building, 147 Hoang Quoc Viet street, Cau Giay District, Ha Noi city, Vietnam

Hai Phong

LGE Factory - Tràng Duệ Industrial - An Dương District, Hải Phòng City

Da Nang

Văn phòng đối tác (HVN) 305 - Nguyễn Tất Thành - Hải Châu - Đà Nẵng

Ho Chi Minh Office

17th floor, Empress building, 138-142 Hai Ba Trung street, Da Kao ward, Distric 1, Ho Chi Minh city, Vietnam