Wiring | 3P3W (2PT-D), 3P4W (3PT-Y) |
---|
Rating | Frequancy | 60Hz, 50Hz Note) |
---|
Voltage | PT | 110V (55~125V) |
---|
GPT | Vn*√3 Vn: PT secondary rating voltage |
---|
Current | CT | 5A |
---|
ZCT | 1.5mA |
---|
Power | AC/DC110V, DC125V |
---|
Power consumption | 30W or less: Stanby / 50W or less: Operation |
---|
Burden | 0.5VA or less: PT 1.0VA or less: CT |
---|
Input contact | for general | Digital Input AC/DC 110V, DC125V |
---|
Output contact | for trip | AC 250V 15A/DC 30V 15A, Resistive Load: Rated Capacity AC 4000VA, DC 480W: Opening Capacity |
---|
for alarm | AC 250V 10A/DC 30V 10A, Resistive Load: Closed Capacity AC 1250VA, DC 150W: Opening Capacity |
---|
Tolerance | Operation Value | ±5% |
---|
Operation Time | ±5% or ±35ms |
---|
OInsulation Resistance | DC 500V 100MΩ or more |
---|
Insulation Voltage | AC 2kV (1kV)/1min |
---|
Lightning impulse voltage | AC 5kV (3kV) or more, 1.2x50μs standard waveform supplied |
---|
Overload withstand | Current circuit | Withstand 1.2 times of rated current continuously Withstand 2 times of rated current for 3 hours. Withstand 20 times of rated current for 2 seconds. Withstand 40 times of rated current for 1 second. |
---|
Voltage circuit | Withstand 1.15 times of rated voltage for 3 hours. |
---|
Fast Transient Disturbance | 4kV: power input 2kV: other input |
---|
Electrostatic Discharge (ESD) | 8kV: Air, 6kV: Contact |
---|
Temperature | Operation | -25℃ ~ 60℃ |
---|
Storage | -40℃ ~ 70℃ |
---|
Humidity | RH 80% or less (non-condensing) |
---|
Altitude | 2,000m or less |
---|
Environment | A place not subject to abnormal vibration and shock. |
---|
Applied Standards | KEMC 1120 |
---|
Dimension (mm) | 196 (W) x 254 (H) x 220 (D): Cutting Size |
---|
Weignt | 6.78kg |
---|
Communication | RS-485: Modbus |
---|