Enclosure
- Compartmented substation could be operated remotely
- 2.3mm thick steel enclosure is mounted on a 6mm thick hot-dip galvanized channel base
- Access to the MV, LV, and Tr. compartments by two double doors
- Protection degree:
- IP 54 (MV and LV compartments)
- IP 31 (transformer compartment)
- IK 10 (mechanical resistance to impact)
- Approximate weight with equipment: Max. 6t (depending on KVA)
- Withstanding internal arc: IAC–AB (21kA1s)
- Four lifting points on the roof are provided for lifting the substation
Equipment
- MV switchgear: Susol RMU (LCL or LFL)
- MV interconnection: 95mm2 XLPE insulated copper cables
- Transformer: Oil (250~1000kVA)
- LV interconnection: Copper busbars
- LV switchboard: One main MCCB and several feeder MCCB
- Earthing circuit, internal lighting
- Optional equipment